Study of the Effects of Fluorescence UV Radiation and Low Temperature on PVC Cable Outer Sheaths

##plugins.themes.academic_pro.article.main##

Moumita Naskar
P. N. Ashitha
K. G. Rakesh

Abstract

Underground Polyvinylchloride (PVC) sheath power cables are exposed to the atmospheric condition during installation. Depending on the atmospheric conditions the cable sheath is facing extreme environmental stresses such as ambient temperature (high and low), direct sunlight (UV) radiation, rain or water accumulation etc. The life of PVC cables is reduced by being exposed to harsh environmental conditions and can subsequently damage the unprotected cables. This work is aimed to the study of the effects of UV radiation and low temperature on PVC cable outer sheaths. Three commercially available PVC cable were chosen for the study. UV exposed PVC insulations become brittle after UV exposure and in low temperature. UV exposure eventually results in material degradation, diminishing the performance characteristics of the material. Thermogravimetric Analysis (TGA) was used to characterize the thermal behavior of PVC cable insulation materials before and after UV ageing. In addition, Fourier-transform infrared spectroscopy (FTIR) was used to reveal the chemical processes that caused the UV degradation of the sample. A good agreement between results of the methods was found. Exposure to low temperature resulted in a reduction in stiffness of the polymeric structure caused embrittlement which transformed the PVC structure from a flexible material capable of undergoing large strain elastic behaviour to a stiffer material with higher yield behaviour.

##plugins.themes.academic_pro.article.details##

How to Cite
Naskar, M., Ashitha, P. N., & Rakesh, K. G. (2018). Study of the Effects of Fluorescence UV Radiation and Low Temperature on PVC Cable Outer Sheaths. Power Research - A Journal of CPRI, 143–147. https://doi.org/10.33686/pwj.v14i2.144712

References

  1. Brebu M, Vasile C, Antonie SR, Chiriac M, Precup M, Yang J, Roy C. Study of the natural ageing of PVC insulation for electrical cables. Polymer Degradation and Stability. 2000; 67:209–21. https://doi.org/10.1016/S01413910(99)00114-7
  2. Linde E, Gedde UW. Plasticizer migration from PVC cable insulation - The challenges of extrapolation methods. Polymer Degradation and Stability. 2014; 101:24–31. https://doi.org/10.1016/j.polymdegradstab.2014.01.021
  3. Arora R, Tripathi V. Effect of ultra violet irradiation on low voltage cable insulation. Conference Record of the 2004 IEEE International Symposium on Electrical Insulation, Indianapolis, IN USA; 2004; 19-22:358–61.
  4. Benes M, Milanov N, Matuschek G, Kettrup A, Placek V, Balek V. Thermal degradation of PVC cable insulation studied by simultaneous TG-FTIR and TG-EGA methods. Journal of Thermal Analysis and Calorimetry. 2004; 78:621–30. https://doi.org/10.1023/B:JTAN.0000046123.59857.ad
  5. Hutabarat JTP, Wirjosentono B, Marpaung H, Agusnar H. The study of degdradation cable isolation of PVC (Polyvinil Chloride): A comparison of isolation cable between short circut and open flame. Chemistry and Materials Research. 2016; 8(12):8–22.