IEC 61850 Client Redundancy for Substation Automation System

##plugins.themes.academic_pro.article.main##

Sudhir Kumar Bai
Gaurav Kanaujia

Abstract

This paper presents an overview of System level redundancy implementation in an IEC61850 based Client application and method used to reduce recovery time after failure of the station level application (IEC 61850 Client, HMI and Database). The authors have presented the implementation of a dual Server hot-standby redundancy architecture, Network Driver (NDIS-Network Driver Interface Specification) for heartbeat communication, network teaming for redundant network redundancy and database replication for substation data integrity and availability of substation data/event. This paper also discusses different redundancy modules (Redundancy Manager, IEC 61850 Client Driver, HMI, Database Module) integration like API integration between Network driver (NDIS) and IEC 61850 Client application. The implementation of data queue in IEC 61850 Client to avoid data loss during server switch over is discussed in this paper. The authors have presented the various fail-over mechanisms in this system. As the redundancy has a direct impact on the cost and complexity of the system, the proposed solution in this paper has addressed the needs of application criticality and customer requirements.

##plugins.themes.academic_pro.article.details##

How to Cite
Kumar Bai, S., & Kanaujia, G. (2017). IEC 61850 Client Redundancy for Substation Automation System. Power Research - A Journal of CPRI, 525–532. Retrieved from https://node6473.myfcloud.com/~geosocin/CPRI/index.php/pr/article/view/1015

References

  1. Carlos Rodriguez, Javier Figuera, Daniel Prieto, Rodolfo Pereda and Aitz Amezaga “Redundancy challenges on IEC 61850 systems and Migration Paths for IEC 61850 Substation Communication Networks”, Cigre, Paris-2012, B5-109.
  2. R. Moore, “Substation LAN - Issues to Consider when Designing and Deploying the Ethernet Network”, Praxis Profiline, April 2007.
  3. Network redundancy in substation applications by Clemens Hoga, Siemens AG Germany, Energy D EA PRO LM 2.
  4. “Performance of the Rapid Spanning Tree Protocol in Ring Network Topology” by Michael Pustylnik, Mira Zafirovic-Vukotic, Roger Moore.
  5. Articles in Journals:
  6. Communication networks and systems in substations – Part 7-4: Basic communication structure for substation and feeder equipment –Compatible logical node classes and data classes, IEC 61850-7-4, 2004-05, 1st ed.
  7. Websites:
  8. https://msdn.microsoft.com/en-us/library/windows/hardware/ff565949(v=vs.85).aspx for NDIS Minport driver communication.
  9. http://www.lefred.be/node/45 for MySQL Master-Master Replication.
  10. Books:
  11. IEC 61850 Standards.
  12. H. Kirrmann, P. Rietmann, S. Kunsman, “Standard Network Redundancy Using IEC 6243”, PAC World Magazine, autumn 2008, pages 38-44.